FMS-FCU-1310
PREVENTIVE MAINTENANCE
MAXIMUM EFFICIENCY
DESCRIPTION
The FCU 1310 is a portable service unit and is designed for temporary measurement of solid particle contamination and water saturation in diesel storage, diesel transfer and diesel filling applications. Measuring contamination levels of diesel fuel, as well as mineral based hydraulic oils compatible with Viton® seals. The FCU 1310 is not compatible with water glycol fluids.
TECHNICAL SPECIFICATION
Self-Diagnosis | Continuously with error indication via status LED and display |
Measured Value | ISO code / SAE Class / NAS Class / Saturation Level / Temperature |
Measuring Range | Display from ISO code 9/8/7 (MIN) to ISO code 25/24/23 (MAX) |
Calibrated within the range ISO 13/11/10 to 23/21/18 | |
Saturation level 0 to 100 % / | |
Temperature -13°F to 212°F (–25°C to 100°C) | |
Accuracy | ± 1/2 ISO class in the calibrated range / ± 2 % Full scale max |
for Water Sat. and Temp. | |
Material of Sealings | FPM seals |
Ambient Temperature Range | 32°F to 113°F (0°C to 45°C) |
Storage Temperature Range | -40°F to 176°F (-40°C to +80°C) |
Dimensions (cover closed) | 9.06” H x 16.14” L x 13”D |
IP Class | IP50 in operation, IP67 when closed |
Weight | Approx. 29 lbs (13 kg) without accessories |
With Diesel According to | IN: 0 psi (0 bar) |
ASTM D975 4-D or DIN EN 590 | OUT: 0 psi (0 bar) |
HYDRAULIC DATA
Hydraulic Fluid | IN: -7.25 to 650 psi (-0.5 to 45 bar) |
Operating Pressure | OUT: 0 to 7.5 psi (0 to 0.5 bar) |
with Adapter for Pressure Lines | IN: 217 to 5000 psi (15 to 345 bar) |
OUT: 0 to 7.5 psi (0 to 0.5 bar) | |
Pressure Max. | 5000 psi (345 bar) |
Permissible Viscosity Range | 33 to 1622 SUS (1.5 to 350 cSt) |
Fluid Temperature Range | 32°F to 158°F (0°C to +70°C), or up to 113°F (45°C) for diesel fuel |