Skip to content

FMS-350-BP/S1-C70-BP/S3

productos-350-s1-c70-s3

FMS-350-BP/S1-C70-BP/S3

ULTRA CLEAN
AND DRY DELIVERY

DESCRIPTION
FMS Filtering Systems has proven in the field to deliver Ultra-clean Ultra-dry diesel with better than ISO 11/8/7 fuel cleanliness levels, under harsh operating conditions, in a single pass, resulting in maximum engine power with a perfect performance. FMS ultra-filtration means optimal handling and control of particulate and water contamination of diesel fuel, which is a must in modern engines that handle very tight tolerances and very high injection pressures.
HOUSING TECHNICAL SPECIFICATION
Max. Flow per Housing  Up to 210 gpm
Porting  3″ NPT
Additional Ports  Particulate filter: 2x test points, 2x
  manometers, 1x Delta P indicator (pop-up or sensor)
  Coalescing filter: 2 x ¼” NPT (US & DS)
Elements Options FMS-1/350-P – FMS-C70-BPE
Max. Operating Pressure 100 psi (7 bar)
Min. Yield Pressure 400 psi (28 bar)
Temperature Range -32°F to 165° (0°C to 74°C)
Bypass Setting Particulate filter: 15 psi (1.03 bar)
Coalescing filter: 25 psi (2 bar)
Porting Head Anodize Aluminum
Element Case Epoxy Paint w/High-phos Electroless
Nickel Plating
Cap Plated Steel
Weight 751 lbs
Element Change Clearance 33.8″ (858 mm)

ELEMENT TECHNICAL SPECIFICATIONS FMS-1/350-P

Efficiency  Beta 4>4193 (ISO 16889:99)
DHC  3000 grams (MTD)
Maximum Pressure  150 psi
Recommended Flow  350 gpm
Dimensions 42×6.25×6.25”
Weight 21 lbs
Housings FMS-350-BP

ELEMENT TECHNICAL SPECIFICATIONS FMS-C70-BPE

Efficiency  98.6% SAE J1488 Certified
DHC  Drain
Maximum Flow 80 gpm
Recommended Flow  70 gpm
Dimensions 40x6x6″
Weight 18 lbs
Housings FMS-C70-BP

Related Products